Invensys TRICONEX HCU3700/3703E Isolated Analog Input Module
3703E Analog Input (AI) Modules includes three independent input channels. Each input channel receives variable voltage signals from each point, converts them to digital values, and transmits the values to the three Main Processor modules on demand. In TMR mode, one value is then selected using a midvalue selection algorithm to ensure correct data for every scan.
Sensing of each input point is performed in a manner that prevents a single failure on one channel from affecting another channel. Each Analog Input Module sustains complete, ongoing diagnostics for each channel. Failure of any diagnostic on any channel activates the Fault indicator for the module, which in turn activates the chassis alarm signal. The module's Fault indicator merely reports a channel fault, not a module failure-the module can operate properly with as many as two faulty channels.
3703E Analog Input Modules support hotspare capability, which allows online replacement of a faulty module.
3703E Analog Input Modules require a separate external termination panel (ETP) with a cable interface to the Tricon backplane. Each module is mechanically keyed for proper installation in a Tricon chassis.
3703E image is for reference only product style, specific data of manufacture and product version, please refer to the actual product delivery!
HCU3700/3703E Analog Input Module SpecificationsModel Number | 3700/3700A | 3701 | 3703E |
Voltage | 0-5V, + 6% (only 3700A) | 0-10V | 0-5V or 0-10V,+6% |
Type | TMR, AI | TMR, AI | TMR, AI |
No. of Input Points | 32; diff, DC coupled | 32, diff, DC coupled | 16, diff, isolated |
Isolated Points | No | No | Yes |
Input Update Rate | 55 ms | 55 ms | 50 ms |
Resolution | 12 bits | 12 bits | 12 bits |
Accuracy | <.15% of FSR, from 0° to 60-C | < .15% of FSR, from 0* to 60-C | <.15% of FSR, from 0* to 60-C |
Input Resistance (load) | 30 MQ (DC), min. | 30 MQ (DC), min. | 30 MQ (DC), min. |
Power-Off Resistance | 30 KQ (DC), typical | 30 KQ (DC), typical | 30 MQ2 (DC), min. |
Common Mode Rejection | -80 dB (DC-100Hz), | -80 dB (DC 100Hz), | -90 dB @ 60Hz, min. |
typical | typical | -100 dB @ DC, min. | |
Common Mode Range | -12V to +12V peak | -12V to +12V peak | +200V peak |
Leg-to-Leg Isolation | 200 KQ typical | 200 K2 typical | 20 K9 typical |
Normal Mode Rejection | |||
@ 8Hz | -3 dB | -3 dB | -3 dB |
@ 60Hz | -17dB | -17 dB | -17 dB |
@ 120Hz | -23 dB | -23 dB | -23 dB |
Input Overrange | 150 VDC115 VAC | 150 VDC/115 VAC | 150 VDC115 VAC |
Protection | contimuous | continuous | continuous |
Current Range | 0-20 mA, | 0-20 mA, | 0-20 mA, |
2502 shunt | 5002 shunt | 250 Q shunt for 5V 500Q2 shunt for 10V | |
Diagnostic Indicators | |||
Module Status | Pass, Fault, Active | Pass, Fault, Active | Pass, Fault, Active |
Color Code | Yellow | Light yellow | Mustard yellow |
Q: Is your product new or refurbished?
A: All our products are original new with one year warranty.
Q: How many days the goods will arrive my hands if I place the order now?
A: As soon as we receive the payment, I will ship the products immediately.
It usually take 3-5 days from China to your hands.
Q: Could you give me some discount?
A: Contact Stella to get more discount for 3703E
Q:Can you ship the goods to my country?
A: Pls don't worry ,We can ship the goods to worldwide
Q:What payment mothod we used?
A:We usually use T/T (Telegraphic Transfer),and we can received with in 1-2days
Q:Can I contact you on Email?
A: You can contact me online to get my email add
TRICONEX | RO3451 | TRICONEX | 8311 | TRICONEX | 3008N |
TRICONEX | MP3101 | TRICONEX | 8310 | TRICONEX | 3008 |
TRICONEX | HCU3700/3703E | TRICONEX | 8300A | TRICONEX | 3006 |
TRICONEX | EMPII 3006 | TRICONEX | 7400213-100 | TRICONEX | 3805E |
TRICONEX | DO3201 | TRICONEX | 7400210-010 | TRICONEX | 3721 |
TRICONEX | DI3301 | TRICONEX | 7400209-030 | TRICONEX | 3708E |
TRICONEX | CM2201 7400206-100 | TRICONEX | 7400209-030 | TRICONEX | 3706A |
TRICONEX | AI3351 | TRICONEX | 7400209-010 | TRICONEX | 3703E |
TRICONEX | AI3281 | TRICONEX | 7400208C-020 | TRICONEX | 3700A |
TRICONEX | AI3351 | TRICONEX | 7400208B-020 | TRICONEX | 3664 |
TRICONEX | 9853-610 | TRICONEX | 7400208-020 | TRICONEX | 3636R |
TRICONEX | 9771-210 | TRICONEX | 7400207-001 | TRICONEX | 3625N |
TRICONEX | 9761-210 | TRICONEX | 7400169-310 9662-1XX | TRICONEX | 3625A |
TRICONEX | 9760-210 | TRICONEX | 4351A | TRICONEX | 3625 |
TRICONEX | 9753-110 | TRICONEX | 4329 | TRICONEX | 3604E |
TRICONEX | 9674-810 | TRICONEX | 4210 | TRICONEX | 3601E |
TRICONEX | 9668-110 | TRICONEX | 4201N | TRICONEX | 3533E |
TRICONEX | 9662-610 | TRICONEX | 4200N | TRICONEX | 3511 |
TRICONEX | 9662-110 | TRICONEX | 4119A | TRICONEX | 3510 |
TRICONEX | 9563-810 | TRICONEX | 4000212-002 | TRICONEX | 3503E |
TRICONEX | 8312 | TRICONEX | 4000103-520 | TRICONEX | 3502EN2 |