PLC Module F4204 F6214 F7105A F7541 F7546 F8620 F8641 F8651E Safety-related Digital Utputs I/O Bus Coupling Module Brand New
F 6214
F 6214: 4 fold analog input module, safety related for transmitters in two-wire technique 4...20 mA, voltage inputs 0...1/5/10 V, current inputs 0...20 mA, with safety isolation resolution 12 bits requirement class AK 1 ... 6

F 7105A
6fach Stromverteiler F 7105A
mit Sicherungsüberwachung und LED-Anzeige
6-fold current distribution F 7105A
with fuse monitoring and LED display
Die Baugruppe hat sechs abgesicherte Strompfade, zum Leitungsschutz und für die Versorgung der Baugruppenträger.
Sicherungen max. 4 A-T (Lieferzustand)
Ausgang potentialfreier Umschaltkontakt
Relaisdaten: s. Rückseite
Schaltzeit ca. 60 ms
Betriebsdaten 24 V = / -15...+20 %,
wss < 15 %, 65 mA
Umgebungsklima -25...+70 °C
Raumbedarf 4 TE - H 100 F 32.101
The module has six fused current paths providing the line protection and the power supply for the module subframes.
Fuses max. 4 A-T (delivery state) floating changeover contact
Relay data: cf. reverse
Switching time approx. 60 ms
Operating data 24 V DC / -15...+20 %, rpp < 15 %, 65 mA
Ambient conditions -25...+70 °C
Space requirement 4 TE - H 100 F 32.101
F 7541
F 7546
Technical Specifications
•Number of Channels: 2
•Input Voltage: 24 V DC
•Output Current: 2 A per channel
•Input/Output Type: Safety Input/Output
•Diagnostic Functions: Supported
•Dimensions: 120 × 80 × 35 mm
•Weight: 400 g
Features
•Redundant design enhances system safety
•Diagnostic functions support real-time monitoring of module health status
•Compact and lightweight design for easy installation and maintenance
F 8651E
Central modules: F 8650E / F 8650X, F 8651E / F 8651X, F 8652E / F 8652X, F 8653E / F 8653X
Battery: CR 2477N, HIMA part no. 44 0000018
It is recommended to change the buffer battery (CPU in operation, modules with voltage feeding) at the latest after 6 years, or with display BATI within three months.
Central Modules
F 8650E / H51q-MS, -HS, -HRS SIL 3 1002D processor
F 8650X
F 8651E / H51q-M, -H, -HR
F 8651X
F 8652E / H41q-MS, -HS, -HRS SIL 3 1002D processor
F 8652X
F 8653E / H41q-M, -H, -HR
F 8653X
Earthing of the 24 VDC System Voltage
Please regard the requirement of the SELV (Safety Extra Low Voltage) or PELV (Protective Extra Low Voltage). To improve the electromagnetic compatibility an instrument earth is provided. The instrument earth is designed within the cabinet in such a way that it fulfills the requirements of a protection earth. All H41q/H51q systems can be operated with earthed L- or not earthed.
Earthed Operation
It is premised that the earthing conditions are excellent and there is a separate earth connection (if possible) through which no external currents flow. Only the earthing of the negative pole (L-) is permitted. Earthing of the L+ positive pole is not admissible, as any earth fault on a sensor line would result in an overriding of the sensor concerned. L- may only be earthed at one point within the system. Generally L- is earthed directly behind the power supply (e.g. on the bus bar). The earthing should be easy to access and disconnect.
The earthing resistance must be ≤ 2 Ω.
Interconnecting the Earth Terminals of Multiple Switchgear Cabinets
The earth must be with less interference voltage as possible. If this cannot be achieved, a separate earth for the control has to be installed.
Safety Precautions
Observe all local safety requirements and use the protective equipment required on site.
Figure 10: Connection of earth terminals
Shielding of Data Lines in the HIMA Communication Systems
Reliable shielding of data lines in HIMA communication systems is achieved by the following measures:
The connection 1) of the cable shield from the bus subscriber's (H41q, H51q) to the bus terminals (H 7506) is established on the bus subscriber's side. Via the plug case and the metal front plate a connection is established via the PCB layout to the PE cabinet earth. The other side of the cable shield is not connected.The connection 2) of the H 7505 interface converter is also established on one side via the plug case. The connection to the top hat rail is established via the X2/1 5) connection. According to HIMA earthing principles the top hat rail itself is connected to the cabinet earth or optionally, to an instrument earth 6). The connection 4) of the cable shield between the individual H 7506 bus terminals is established on one side via a terminal. The terminal is located on a top hat rail to which it is also conductively connected. The shield of the BV 7044 cable for the connection 3) of the H 7505 interface converter is earthed on the PC (PADT) side. The measures 1), 2), 3) are standardized already finished in HIMA. The connections 4), 5), 6) have to be performed during the installation on site. The shielding connection using a special cable 7) does already exist or has to be performed depending on the special cable.
Figure 2: Connection of the cable shields
Shielding in the Input/Output Area
At installation of the field cables pay attention to the fact, that the cables to sensors and actuators are separated from power supply cables and in a sufficient distance from electromagnetic active devices (motors, transformers). Cables to the input modules of the H41q/H51q systems have to be installed interference-free as possible e. g. as shielded cables. This applies especially to cables with analog signals and for proximity switches.
With cable connectors having a shield termination line this has to be connected to the bus bar of the I/O rack below the slot of the module.
Further informations on the requirements of shielding and earthing you will find in the data sheets of the modules



Q: Is your product new or refurbished?
A: All our products are original new with one year warranty.
Q: How many days the goods will arrive my hands if I place the order now?
A: As soon as we receive the payment, I will ship the products immediately.
It usually take 3-5 days from China to your hands.
Q: Could you give me some discount?
A: Contact Stella to get more discount for F8641
Q:Can you ship the goods to my country?
A: Pls don't worry ,We can ship the goods to worldwide
Q:What payment mothod we used?
A:We usually use T/T (Telegraphic Transfer),and we can received with in 1-2days
Q:Can I contact you on Email?
A: You can contact me online to get my email add
| HIMATRIX | Z7150 | HIMATRIX | F7541 | HIMATRIX | F3226 |
| HIMATRIX | Z7138 | HIMATRIX | F7133 | HIMATRIX | F3221 |
| HIMATRIX | Z7136 | HIMATRIX | F7131 | HIMATRIX | F3113A |
| HIMATRIX | Z7128 | HIMATRIX | F7130A | HIMATRIX | F3 AIO 8/4 01 |
| HIMATRIX | Z7127 | HIMATRIX | F7130 | HIMATRIX | F2201 |
| HIMATRIX | Z7126 | HIMATRIX | F7126 | HIMATRIX | F1101 |
| HIMATRIX | Z7116 | HIMATRIX | F7105A | HIMATRIX | BV7032-0.5 |
| HIMATRIX | Z7108 | HIMATRIX | F6705 | HIMATRIX | 52100 |
| HIMATRIX | Z1006 | HIMATRIX | F6251 | HIMATRIX | F3 DIO 16/801 |
| HIMATRIX | K9203 | HIMATRIX | F6217 | HIMATRIX | F60 MI 24 01 |
| HIMATRIX | K7214 | HIMATRIX | F6215 | HIMATRIX | F6706 |
| HIMATRIX | F60GEH01 | HIMATRIX | F6205 | HIMATRIX | ZI006 |
| HIMATRIX | F3DIO8/801 | HIMATRIX | F4204 | HIMATRIX | F1DI1601 |
| HIMATRIX | F3 DIO 8/8 01 | HIMATRIX | F3430 | HIMATRIX | F3311 |
| HIMATRIX | F2DO1602 | HIMATRIX | F3423 | HIMATRIX | F3225 |
| HIMATRIX | H7506 | HIMATRIX | F3421 | HIMATRIX | F3222 |
| HIMATRIX | F8651E | HIMATRIX | F3417A | HIMATRIX | F3112 |
| HIMATRIX | F8650X | HIMATRIX | F3349 | HIMATRIX | F60DIO24/1601 |
| HIMATRIX | F8641 | HIMATRIX | F3331 | HIMATRIX | F6251 |
| HIMATRIX | F8627 | HIMATRIX | F3330 | HIMATRIX | F60DI3201 |
| HIMATRIX | F8621 F8621/A | HIMATRIX | F3322 | HIMATRIX | F3D/O16/801 |
| HIMATRIX | F8620 | HIMATRIX | F3237 | HIMATRIX | F3417A |
| HIMATRIX | F7553 | HIMATRIX | F3236 | HIMATRIX | F6214 |
| HIMATRIX | F1DI16 01 | HIMATRIX | F3334 | HIMATRIX | F8627X |
| HIMATRIX | F8628X | HIMATRIX | F3AIO8/401 | HIMATRIX | F3 DIO 8/8 01 |
| HIMATRIX | F60 DIO 24/16 | HIMATRIX | F2 DO 16 02 | HIMATRIX | F60 GEH 01 |